On-line PD Testing of HV Transformers
As HV transformers are oil-filled it is not usual for them to
discharge in the main tank or windings as the oil 'quenches' any PD
activity here.
PD activity does occur in the HV bushings of transformers which can
be detected using internal bushing 'taps' or, in some cases with
external TEV sensors placed at the bottom of the bushings. PD 'TEV'
signals will only come out of the transformer if it has insulated
gaskets, either at the bushings or the input/output points. If there
are no insulated gaskets and the transformer is fully metal
enclosed, this acts as a Faraday Cage with all PD signals held
within the Transformer.
Location of the origin of a PD site can be made with distributed TEV
probes on the LV and HV side, if there are suitable 'pathways' for
the PD signals to come out of the transformer. It is now becoming
popular to include internal Capacitive Coupler Bushing 'Taps' in HV
Transformer bushings and also UHF Coupler 'Windows' in the main tank
to 'look into' the transformer to detect PD in the both the bushings
and main tank.
Figure 1. Diagram of the 275kV Cable Sealing Ends and HV transformer links
Recommendations for HV Transformer Partial Discharge
Monitoring
- Regular PD testing and monitoring of the HV transformers should
be made to ensure trouble free service operation of the high
voltage components. Monthly testing seems as frequent as
operationally convenient, but the risks of service trouble is
always higher after commissioning, so perhaps a sliding scale
could be applied, with more frequent measurements at the start,
becoming less frequent as the system beds down without
incident.
- There is a real challenge with making On-line PD measurements at
HV voltages of 110kV+ as we need to measure very small events in
generally large noise. Any new capability which will help look
for PD activity which is small (i.e. below 100pC) should be
used. Transformer owners should make sure that new methods of
analysing PD data and removing noise are implemented. Training
in PD measurements for the staff is a vital part in keeping the
high voltage systems discharge free.
- Some thought could be given to fitting permanent PD sensors
inside the transformers. This would have the advantage that
they could be calibrated, and could be inside the faraday cage
of the transformer, and hence be free of interfering noise
external to the transformer. Such systems in the form of
internal UHF Capacitive Couplers are routinely fitted into GIS
switchgear at manufacture and this technology has recently been
applied successfully to HV transformers.